RCS-923A断路器失灵及辅助保护装置 下载本文

内容发布更新时间 : 2024/11/2 15:18:19星期一 下面是文章的全部内容请认真阅读。

南瑞继保电气有限公司版权所有2004.6(V1.0X)

本说明书和产品今后可能会有小的改动,请注意核对实际产品与说明书的版本是否相符。

更多产品信息,请访问互联网:http://www.nari-relays.com

目 录

1 概述 ........................................................................................................................................................ 1 1.1 应用范围 ......................................................................................................................................... 1 1.2 保护配置 ......................................................................................................................................... 1 2 技术参数 ................................................................................................................................................ 2 2.1机械及环境参数 .............................................................................................................................. 2 2.2 额定电气参数 ................................................................................................................................. 2 2.3 主要技术指标 ................................................................................................................................. 2 3 软件工作原理 ........................................................................................................................................ 4 3.1 保护程序结构 ................................................................................................................................. 4 3.2 正常运行程序 ................................................................................................................................. 4 3.3起动元件 .......................................................................................................................................... 5 3.4 失灵起动 ......................................................................................................................................... 5 3.5过流保护 .......................................................................................................................................... 6 3.6三相不一致保护 .............................................................................................................................. 6 3.7充电保护 .......................................................................................................................................... 6 3.8跳闸逻辑 .......................................................................................................................................... 6 3.9工作逻辑方框图 .............................................................................................................................. 7 4 硬件原理说明 ........................................................................................................................................ 8 4.1 装置整体结构 ................................................................................................................................. 8 4.2 装置面板布置 ................................................................................................................................. 9 4.3 装置接线端子 ................................................................................................................................. 9 4.4 输出接点 ....................................................................................................................................... 10 4.5 结构与安装 ................................................................................................................................... 10 4.6 各插件原理说明 ........................................................................................................................... 11 5 定值内容及整定说明 .......................................................................................................................... 18 5.1 装置参数及整定说明 ................................................................................................................... 18 5.2 保护定值及整定说明 ................................................................................................................... 19 5.3 压板定值 ....................................................................................................................................... 19 5.4 IP地址 ......................................................................................................................................... 20

NARI-RELAYS RCS-923A型断路器失灵及辅助保护装置

RCS-923A断路器失灵及辅助保护装置

1 概述

1.1 应用范围

本装置为由微机实现的数字式断路器失灵起动及辅助保护装置,也可作为母联或分段开关的电流保护。

1.2 保护配置

RCS-923A 是由微机实现的数字式断路器失灵起动及辅助保护装置,也可作为母联或分段开关的电流保护。装置功能包括失灵起动、三相不一致保护、两段相过流保护和两段零序过流保护、充电保护等功能,可经压板和软件控制字分别选择投退。

1.3 性能特征

? 装置具有失灵起动功能,其分相判别的相电流元件动作后,输出两组起动接

点,与外部保护动作接点串联后在线路、母联或分段断路器失灵时去起动失灵保护。

? 装置具有三相不一致保护功能,当断路器某相断开,线路上出现非全相时,

可经三相不一致保护回路延时跳开三相,三相不一致保护功能可由控制字选择是否经零序或者负序电流开放。

? 装置具有带延时的过流保护功能(两段相过流、两段零序过流)。

? 装置具有充电保护功能,当向故障母线(线路)充电时,可及时跳开本断路

器。

? 装置采用整体面板、全封闭机箱,强弱电严格分开,取消传统背板配线方式,

同时在软件设计上也采取相应的抗干扰措施,装置的抗干扰能力大大提高,对外的电磁辐射也满足相关标准。

? 完善的事件报文处理,可保存最新128次动作报告,24次故障录波报告。 ? 友好的人机界面、汉字显示、中文报告打印。

? 灵活的后台通信方式,配有RS-485通信接口(可选双绞线、光纤)或以太网。 ? 支持电力行业标准DL/T667-1999(IEC60870-5-103标准)的通信规约。 ? 与COMTRADE兼容的故障录波。

- 1 -