箱变操作使用说明 - 图文 下载本文

内容发布更新时间 : 2024/5/19 9:12:07星期一 下面是文章的全部内容请认真阅读。

TZBWO-12铁路电力远动智能箱变

安装使用与维护手册

Railway Remote Intelligent Compact Substation

Instruction manual

青岛特锐德电气有限公司 TGOOD ELECTRIC CO.,LTD QINGDAO

始终安全第一

Safety first-always!

在开关设备安装使用前请先仔细阅读本说明书

That’s why our instruction manual begins with these recommendations

箱式变电站安装于户外场所。

Compact substation install outdoor suitable for electrical equipment. 确保由专职电气人员进行安装、操作和维护。

Ensure that installation,operation and maintenance are carried out by specialist electricians only.

必须保证现场电气设备的联接条件和工作规程的适用和安全性。

Comply in full with the legally recognized standards(DIN VDE/IEC),the connection conditions of the local electrical utility and the applicable safety at work regulations.

有关开关设备的一切操作,都要遵守说明书中的相应规定。

Observe the relevant information in the instruction manual for all actions

involving switchgear and switchboards. 危险 Danger

要特别注意说明书中标有这个危险标志的注意事项。

Pay special attention to the hazard notes in the instruction manual marked with this warning symbol.

不要超出开关设备在正常工作条件下的技术参数里规定的负载。

Make sure that under operation condition of the switchboard the specified data are not exceeded.

说明书应放在所有与安装、操作和维护有关人员能方便地拿到的地方。 Keep the instruction manual accessible to all persons concerned with installation, operation and maintenance.

用户的专职人员应对所有影响工作安全的事项负责,并正确管理开关设备。 the user’s personnel are to act responsibly in all matters affecting safety at work and the correct handing of the switchgear.

若对本说明书尚有疑问,我们将很乐意提供进一步的资讯。

If you have any further questions on this instruction manual, we will be pleased to provide the required information.

目 录

contents.............

一 产品概述 ..................................................................................................................................... 4 二 铁路电力远动智能箱变的功能 ................................................................................................. 4 三 箱变主要技术指标、标准及使用环境 ..................................................................................... 5

1.箱变重要技术参数 ............................................................................................................... 5 2.使用环境条件 ....................................................................................................................... 5 四 质量保证及客户服务 ................................................................................................................. 6 五 安全规程 ..................................................................................................................................... 7

1.运输和吊装 ........................................................................................................................... 7 2.交货和中间保管 ................................................................................................................... 7 3.现场安装 ............................................................................................................................... 8 4.操作 ..................................................................................................................................... 10 5.箱变运行 ............................................................................................................................. 10 6.高压安全原则 ..................................................................................................................... 10 六 箱变的组成、布局及配置 ....................................................................................................... 11 七 高压环网开关柜 ....................................................................................................................... 14

1.MINEX/GISELA系列SF6绝缘环网柜 ................................................................................ 14 2.技术参数 ............................................................................................................................. 15 3.高压环网柜操作 ................................................................................................................. 16 4.开关操作 ............................................................................................................................. 16 5.高压熔断器的更换 ............................................................................................................. 20 6.电动操作机构 ..................................................................................................................... 21 7.辅助二次回路的连接 ......................................................................................................... 22 8.母线PT ................................................................................................................................ 22 八 变压器单元 ............................................................................................................................... 23 九 低压配电柜 ............................................................................................................................... 25

1.进线隔离开关 ..................................................................................................................... 25 2.出线断路器 ......................................................................................................................... 26 3.低压计量 ............................................................................................................................. 29 4.低压测量及指示 ................................................................................................................. 29 5.低压室自动温控系统和防凝露系统 ................................................................................. 30 6.端子柜的设置 ..................................................................................................................... 30 十 辅助系统设计 ........................................................................................................................... 31 十一 直流屏 ................................................................................................................................... 32 十二 调试和试验 ........................................................................................................................... 33 十三 安装、运行与检修注意事项 ............................................................................................... 34 十四 常见问题处理 ....................................................................................................................... 37

一 产品概述

TZBWO-12系列铁路电力远动智能箱变是针对铁路系统供电特点而专门设计的高新技术产品。铁路线路主要为铁路系统调度集中、大站电气集中联锁、自动闭塞、驼峰信号等I级负荷提供电源。这两条线路及向这两条线路供电的变、配电所一旦发生故障,将造成信号灯灭、列车堵塞等事故,打乱运输计划,甚至出现难以挽回的经济损失。铁路电力远动箱变就是将高压环网柜、信号变压器、低压开关柜、直流屏、RTU控制部分等部分有机的组合在一起。结构紧凑,安全可靠,不受外界干扰,功能扩展空间大,不仅能够对信号电源实时监控还能够通过RTU装置进行故障录波。通过小电流系统直接判断接地故障区间,还能进行远程抄表。检修集中、简单,占地面积少,不受恶劣环境的侵害。

二 铁路电力远动智能箱变的功能

1. 为铁路系统调度集中、大站电气集中联锁、自动闭塞、驼峰信号等I级负荷提供电源;

2. 确保铁路信号系统安全用电; 3. 倒闸操作,就地控制功能; 4. 高低压电源的自动投切; 5. 实时监测,主站调度; 6. 故障报警,故障录波;

7. 实现“三遥”(遥测、遥信、遥控); 8. 参数设定,定值调整;

三 箱变主要技术指标、标准及使用环境 1.箱变重要技术参数

☆ 额定电压:12kV/400V

☆ 额定电流:高压630A;低压200A ☆ 额定容量:2×20(80、100)kVA ☆ 工频耐压:高压42kV;低压2500V

☆ 额定热稳定电流:高压回路20kA/2S;低压回路30kA/1S ☆ 额定动稳定电流:高压回路50kA;低压回路63kA ☆ 雷电冲击:高压75kV ☆ 箱变温升:不大于60℃ ☆ 防护等级:IP54

☆ 监测回路电压电流精度:1.0级

☆ 交流电流每回路功率损耗小于0.75VA,交流电压每回路功率损耗

小于0.5VA

☆ 箱变接地电阻小于1Ω

2.使用环境条件

☆ 海拔不超过1000m。

☆ 周围空气温度不高于+50℃;不低于-30℃。 ☆ 户外风速不超过35m/s。

☆ 相对湿度:日平均值不大于95%,月平均值不大于90%。

☆ 安装地点:安装在没有火灾、爆炸危险、严重污秽、化学腐蚀及剧烈

震动场所。